Place of Origin: | China |
Brand Name: | Chuangyin |
Certification: | KEMA/type test report |
Model Number: | OMB-17.5F (JLSZXW3-17.5F) |
Minimum Order Quantity: | 1 pc |
---|---|
Price: | Negotiable |
Packaging Details: | Polywood |
Delivery Time: | 5-10 workdays |
Payment Terms: | L/C, T/T |
Highest Voltage For Equipment Um (r.m.s.): | 17.5kV | Rated Frequency: | 50, 60 Or 50/60 |
---|---|---|---|
Number Of CTs And VTs: | 3VT+3CT | Rated Primary Current: | 5A Up To 800A |
Rated Secondary Current: | 5Aor1A | Standard: | IEC 61869-1:2007、 IEC 61869-2:2012 IEC 61869-3:2011、IEC 61869-4:2013 IEEE (ANSI) C57.12-2016 |
High Light: | MV Pole Mounted Metering Transformer,17.5kV Pole Mounted Metering Transformer,3CT Metering Box Combination Transformer |
OMD-17.5,OMD-24
Overhead pole mounted primary metering unit
This type of metering box is an outdoor dry-type three-phase primary metering unit. The medium-voltage metering transformer is assembled by 3 single-phase combined transformers. Each single-phase combined transformer contains 1 set of CT coil and 1 set of VT coil, Cyclic epoxy resin (CEP) vacuum casting solid encapsulation, with excellent insulation performance and hydrophobicity, the surface is resistant to acid and alkali corrosion, contamination, and UV. It is suitable for outdoor overhead line installation and connection to public power systems. The metering box has connected the secondary lead of the transformer to the junction box of the centralized terminal. The sealing design of the junction box has an output port to connect with the meter box, which is quick to install. It is suitable for the equipment in the urban and rural power distribution network with the maximal voltage not more than 17.5kV for electric energy metering, current and voltage measurement.
1.General parameters:
No. | item | units | specification |
1 |
Highest voltage for
|
kV | 17.5 |
2 | Rated frequency (fR) | Hz | 50, 60 or 50/60 |
3 |
Rated lightning impulse
|
kV | 95 kV,110 kV |
4 |
Rated power-frequency
|
kV | 38 |
5 |
Rated power-frequency
|
kV | 3 |
6 | Number of CTs and VTs | pcs | 3VT+3CT |
7 | Standard | / |
IEC 61869-1:2007, IEC 61869-2:2012 IEC 61869-3:2011,IEC 61869-4:2013 IEEE (ANSI) C57.12-2016 |
2.Function and application
Overhead pole mounted primary metering unit complies with the latest applicable industrial standards and local and or national electrical code (such as IEC, IEEE (ANSI), CAN, GOST, CEF). It is used for three-phase overhead power grid energy measurement management and distribution network automation management system, the primary side measurement is more accurate, and the power loss of the line can be effectively measured so as to reduce losses.
3.Main features
3.1The medium voltage transformer of the metering unit is composed of 3 single-phase combined transformers, which saves installation space and can be installed directly on the pole outdoors, which is convenient and quick;
3.2The junction box of the metering unit is installed with a test terminal block and the lead wire connected to the transformer, and the junction box door lock seal structure is with anti-electricity stealing design. The metering box can also be equipped with an electric meter box on the pole;
3.3The box is made of corrosion-resistant stainless steel or equivalent performance low-carbon steel with protective coating. The sealing design is weatherproof, acid and alkali corrosion resistant, and UV resistant;
3.4The medium voltage transformer is insulated with epoxy resin solid encapsulation and has excellent dielectric and mechanical performance. It is oil-free, gas-free and maintenance-free, meeting the requirements of safe operation and environmental protection.
3.5The CT of the medium voltage combined transformer can be configured according to double transformation ratios, and the VT is equipped with anti-short circuit and overload protection devices as required to avoid burning and explosion caused by VT short circuit and overload.
3.6The primary connection adopts copper contact bar and terminal clamp and can be equipped with terminal connectors with corresponding area as per user’s requirement. Lightning arrester can be selected as required.
4.Technical parameters.
Current transformer specifications
No | Item | Specification |
|
Rated primary current | 5A up to 800A |
|
Rated secondary current | 5A or 1A |
|
Rated Continuous Thermal Current | 120%,125%,150%,200%,etc. |
|
Rated Short time current (Ith) (thermal 1 second) | 80xIpr,100xIpr |
|
Rated Dynamic Current (Idyn) | 2.5xIth |
|
Rated Output(VA) | 5,10,12.5,15,20 |
|
Accuracy Class | 0.2S,0.2,0.5S,0.5,1 Metering |
|
Instrument Security Factor (FS) | 5,10,20 |
|
Applicable Standard | IEC: 61869-1&2 |
Voltage transformer specifications
No | Item | Specification |
|
Rated primary voltage(V) | 13200/√3,13800/√3, 15000/√3,7200,8400 |
|
Rated secondary voltage(V) | 100/√3,110/√3, 115/√3, 120/√3, 110,115,120 |
|
Rated Voltage Factor |
1.2/Continuous 1.5/30s,1.9/30s,1.9/8h 1.5/30s,1.9/30s,1.9/8h |
|
Standard connection | Y-Y connection |
|
Rated Output(VA) | 15,20,25,30,50,75 |
|
Accuracy Class | 0.2,0.5,1,3 Metering |
|
Thermal burden(VA) | 500 |
|
Applicable Standard | IEC: 61869-1&3 |
If the parameter requested exceeds the range of the above table, it can be determined after negotiation with our company.
5.Dimensions and wiring schematic diagram.
Selective meter box 1 (IEC) can be manufactured as per required sizes
Selective meter box 2 (ANSI) can be manufactured as per required sizes
6.Special instructions.
The company can design and manufacture specially according to the special requirements of customers.
Contact Person: Mr. Dieky Lin
Tel: +86 138 2379 0397
Fax: 86-0755-8600-0614
Light Weight Vacuum Resin Cast Current Transformer Fully Enclosed
36kv Indoor Epoxy resin cast current transformer MV LRZ3-36G Chuangyin
Chuangyin 12kV MV CT Current Transformer for Air Insulation Switchgear
100A/40mA Split Core Current Transformer Open type CT CY-KCT01
Clamp On Split Core Current Transformer Open Distributed Measurement Systems
Epoxy Resin Split Core Current Transducer JDZ-17.5(24) Voltage Transformer Waterproof CT
500A 50/60Hz Open type Split Core Current Transformer Smart Logger
35kV 2# And 3# Plug In euromold termination kit Connector For PT
Epoxy Resin Cast Plug In Bushing GIS IEC 42KV 800A /1250A For Outdoor
42KV 800A /1250A Outdoor GIS Plug In Bushing IEC Epoxy Resin