Place of Origin: | China |
Brand Name: | Chuangyin |
Certification: | KEMA/type test report |
Model Number: | JLSZXW3-17. |
Minimum Order Quantity: | 1 pc |
---|---|
Price: | Negotiable |
Packaging Details: | Polywood |
Delivery Time: | 5-10 workdays |
Payment Terms: | L/C, T/T |
Highest Voltage For Equipment Um (r.m.s.): | 17.5kV | Rated Frequency: | 50, 60 Or 50/60 |
---|---|---|---|
Number Of CTs And VTs: | 3VT+3CT | Rated Primary Current: | 5A Up To 800A |
Rated Secondary Current: | 5Aor1A | Standard: | IEC 61869-1:2007、 IEC 61869-2:2012 IEC 61869-3:2011、IEC 61869-4:2013 IEEE (ANSI) C57.12-2016 |
High Light: | 17.5kV Pole Mounted Metering Box,800A Pole Mounted Metering Box,3VT Single Phase Metering Transformer |
OMB-17.5 (JLSZXW3-17.5)
Overhead Pole Mounted Primary Metering Unit
This type of metering box is an outdoor dry-type three-phase primary metering unit. The medium-voltage metering transformer is assembled by 3 single-phase combined transformers. Each single-phase combined transformer contains 1 set of CT coil and 1 set of VT coil, Cyclic epoxy resin (CEP) vacuum casting solid encapsulation, with excellent insulation performance and hydrophobicity, the surface is resistant to acid and alkali corrosion, contamination, and UV. It is suitable for outdoor overhead line installation and connection to public power systems. The metering box has connected the secondary lead of the transformer to the junction box of the centralized terminal. The sealing design of the junction box has an output port to connect with the meter box, which is quick to install. It is suitable for the equipment in the urban and rural power distribution network with the maximal voltage not more than 17.5kV for electric energy metering, current and voltage measurement.
1.General parameters:
No. | item | units | specification |
1 |
Highest voltage for
|
kV | 17.5 |
2 | Rated frequency (fR) | Hz | 50, 60 or 50/60 |
3 |
Rated lightning impulse
|
kV | 95 kV,110 kV |
4 |
Rated power-frequency
|
kV | 38 |
5 |
Rated power-frequency
|
kV | 3 |
6 | Number of CTs and VTs | pcs | 3VT+3CT |
7 | Standard | / |
IEC 61869-1:2007, IEC 61869-2:2012 IEC 61869-3:2011,IEC 61869-4:2013 IEEE (ANSI) C57.12-2016 |
2.Function and application:
Overhead pole mounted primary metering unit complies with the latest applicable industrial standards and local and or national electrical code (such as IEC, IEEE (ANSI), CAN, GOST, CEF). It is used for three-phase overhead power grid energy measurement management and distribution network automation management system, the primary side measurement is more accurate, and the power loss of the line can be effectively measured so as to reduce losses.
3.Main features
JLSZXW3-17.5 CNAS reporte (2).pdf
JLSZXW3-17.5 KEMA reporte (1).PDF
4.Technical parameters.
Current transformer specifications
No | Item | Specification |
|
Rated primary current | 5A up to 800A |
|
Rated secondary current | 5A or1 A |
|
Rated Continuous Thermal Current | 120%,125%,150%,200%,etc. |
|
Rated Short time current (Ith) (thermal 1 second) |
80xIpr,100xIpr |
|
Rated Dynamic Current (Idyn) | 2.5xIth |
|
Rated Output(VA) | 5,10,12.5,15,20 |
|
Accuracy Class | 0.2S,0.2,0.5S,0.5,1 Metering |
|
Instrument Security Factor (FS) | 5,10,20 |
|
Applicable Standard | IEC: 61869-1&2 |
Voltage transformer specifications
No | Item | Specification |
|
Rated primary voltage(V) | 13200/√3,13800/√3, 15000/√3,7200,8400 |
|
Rated secondary voltage(V) | 100/√3,110/√3, 115/√3, 120/√3, 110,115,120 |
|
Rated Voltage Factor |
1.2/Continuous 1.5/30s,1.9/30s,1.9/8h 1.5/30s,1.9/30s,1.9/8h |
|
Standard connection | Y-Y connection |
|
Rated Output(VA) | 15,20,25,30,50,75 |
|
Accuracy Class | 0.2,0.5,1,3 Metering |
|
Thermal burden(VA) | 500 |
|
Applicable Standard | IEC: 61869-1&3 |
If the parameter requested exceeds the range of the above table, it can be determined after negotiation with our company.
5.Dimensions and wiring schematic diagram.
6.Special instructions.
The company can design and manufacture specially according to the special requirements of customers.
Contact Person: Sales Manager
Tel: +8613823790397
Light Weight Vacuum Resin Cast Current Transformer Fully Enclosed
36kv Indoor Epoxy resin cast current transformer MV LRZ3-36G Chuangyin
Chuangyin 12kV MV CT Current Transformer for Air Insulation Switchgear
100A/40mA Split Core Current Transformer Open type CT CY-KCT01
Clamp On Split Core Current Transformer Open Distributed Measurement Systems
Epoxy Resin Split Core Current Transducer JDZ-17.5(24) Voltage Transformer Waterproof CT
500A 50/60Hz Open type Split Core Current Transformer Smart Logger
35kV 2# And 3# Plug In euromold termination kit Connector For PT
Epoxy Resin Cast Plug In Bushing GIS IEC 42KV 800A /1250A For Outdoor
42KV 800A /1250A Outdoor GIS Plug In Bushing IEC Epoxy Resin